Swami Cables LLP’s 4 Core PVC Round Cables are engineered for reliable and efficient power transmission in submersible pump systems and demanding electrical installations. Manufactured using high-purity annealed copper conductors with premium-grade PVC insulation, these cables ensure excellent conductivity, electrical safety, and long service life. The round construction provides superior flexibility, balanced current distribution, and smooth installation in borewells, conduits, and industrial setups.
Designed to perform consistently in wet, harsh, and continuous-duty environments, our 4 Core PVC Round Cables offer strong resistance to moisture, abrasion, oil, and chemicals. Each cable is produced under strict quality control to deliver stable performance, durability, and compliance with industry standards.
| Core Configuration | 4 Core |
| Conductor Material | Electrolytic Grade Annealed Copper |
| Conductor Construction | Stranded |
| Insulation Type | PVC(Polyvinyl Chloride) |
| Voltage Rating | Up to 1100 V |
| Operating Temperature | Up to 70°C |
| Cable Shape | Round |
| Standard Sizes | 1.5 / 2.5 / 4.0 / 6.0 sq.mm (custom sizes available) |
| "SWAMI CABLES” copper conductor, PVC insulated and Double sheathed 4 core round cable | |||||||||||
| Size / Area in Sq.mm. | No. & size of wire | Nominal Insulation thickness (mm) | Overall core Diameter (mm) | Thickness of inner sheath (mm) | Thickness of outer sheath (mm) | Overall Diameter (mm) | Max. resistance @20°C (ohm/km) | Current rating (Amp.) | |||
| 1.50 | 22/0.30 | 0.60 | 3.00 | 1.00 | 1.20 | 10.80 | 12.10 | 14 | |||
| 2.50 | 36/0.30 | 0.70 | 3.60 | 1.00 | 1.20 | 13.20 | 7.41 | 18 | |||
| 4.00 | 56/0.30 | 0.80 | 4.50 | 1.00 | 1.20 | 14.20 | 4.61 | 25 | |||
| 6.00 | 84/0.30 | 1.00 | 5.20 | 1.00 | 1.40 | 16.50 | 3.08 | 32 | |||
| 10.00 | 140/0.30 | 1.00 | 6.50 | 1.00 | 1.40 | 19.10 | 1.83 | 45 | |||
| Note: Insulation thickness, sheath thickness, and overall dimensions provided in the table are nominal values. The number of strands and strand diameter are designed to meet the conductor resistance requirements as per IS 8130:1984, and the cable conforms to IS 694:2010. | |||||||||||
| Rating Factor for Low Voltage:Multiply the full load current of submersible motor by factors given below for different supply voltage & select right cable. | |||||||||||||||
| Voltage | 415 | 400 | 350 | 300 | 275 | 250 | |||||||||
| Rating factor | 1.00 | 1.05 | 1.15 | 1.25 | 1.3 | 1.35 | |||||||||
| Derating Factors:For varying ambient temperatures, apply the relevant derating factor to the motor full load current to ensure proper cable selection. | |||||||||||||
| Ambient Temperature °C | 30 | 35 | 40 | 45 | 50 | ||||||||
| Rating factor | 1.09 | 1.04 | 1.00 | 0.95 | 0.77 | ||||||||